[Abstract]
Aiming at the common problems of ventilation and air-conditioning system in equipment rooms of subway stations, on the basis of systematic analysis of the current situation and challenges, combining with the development trend of air conditioning in the field of data center–refrigerant pump assisted multi-connected air conditioner, the application scheme of this technology in equipment rooms of subway stations is put forward. Furthermore, standard underground station in a city in north China is taken as an example. A comprehensive technical and economic comparison is made with the traditional scheme. The analysis results show that the scheme has technical advantages in improving room temperature control effect, saving operation energy, ensuring air quality, matching load characteristics, facilitating construction, operation and maintenance, reducing control difficulty and so on. Although the initial investment of the scheme is about 700,000 RMB higher than that of the traditional scheme, the operation cost is about 227,000 RMB lower than that of the traditional scheme. The payback period of the static investment is about 3.1 years, which has a good economy.